INVT Goodrive300 Series Operation Manual page 99

Vfd
Table of Contents

Advertisement

Goodrive300 Series VFD
Function
Name
code
Enable
P08.37
dynamic
braking
Dynamic
braking
P08.38
threshold
voltage
Cooling fan
P08.39
running mode
PWM
P08.40
selection
Detailed instruction of parameters
Output frequency
Set frequency
Y
,
RO1, RO2
Setting range: 0.00Hz–P00.03 (Max. frequency)
This parameter is used to control the enabling of
the internal braking pipe inside the VFD.
0: Disable
1: Enable
Note: This function is only applicable to the
internal braking pipe.
Set the initial bus voltage for dynamic braking.
This value can be adjusted to perform valid
braking on a load. The factory setting changes
with the voltage class.
Setting range: 200.0–2000.0V
To prevent customers from setting a value that is
too large, the following setting ranges are
recommended:
Voltage
380V
Range
685–750V 860–950V 1080–1180V
0: Normal mode
1: The fan keeps running after being powered on.
0x00–0x21
LED ones: PWM mode selection
0: PWM mode 1, three-phase modulation and
two-modulation
1: PWM mode 2, three-phase modulation
LED tens: low-speed carrier frequency limit mode
0: Low-speed carrier frequency limit mode 1, the
carrier frequency will limit to 2k if it exceeds 2k at
low speed
1: Low-speed carrier frequency limit mode 2, the
94
Detectionn range
Time
Time
500V
660
Function parameters
Default
Modify
value
0
380V
voltage:
700.0V
500V
voltage:
900.0V
660V
voltage:
1120.0V
0
01