Function
Name
code
Factory bar
P07.22
code 2
Factory bar
P07.23
code 3
Factory bar
P07.24
code 4
Factory bar
P07.25
code 5
Factory bar
P07.26
code 6
Current fault
P07.27
type
Previous fault
P07.28
type
Previous 2
P07.29
fault type
Detailed instruction of parameters
0x0000–0xFFFF
0x0000–0xFFFF
0x0000–0xFFFF
0x0000–0xFFFF
0x0000–0xFFFF
0: No fault
1: Inverter unit U phase protection(OUt1)
2: Inverter unit V phase protection(OUt2)
3: Inverter unit W phase protection(OUt3)
4: ACC overcurrent (OC1)
5: DEC overcurrent (OC2)
6: Constant-speed overcurrent (OC3)
7: ACC overvoltage (OV1)
8: DEC overvoltage (OV2)
9: Constant-speed overvoltage (OV3)
10: Bus undervoltage (UV)
11: Motor overload (OL1)
12: The VFD overload (OL2)
13: Input side phase loss (SPI)
14: Output side phase loss (SPO)
15: Overheat of the rectifier module (OH1)
16: Overheat fault of the inverter module (OH2)
17: External fault (EF)
18: 485 communication fault (CE)
19: Current detection fault (ItE)
20: Motor antotune fault (tE)
21: EEPROM operation fault (EEP)
22: PID response offline fault (PIDE)
23: Braking unit fault (bCE)
24: Running time arrival (END)
25: Electrical overload (OL3)
26: Panel communication fault (PCE)
86