Goodrive300 Series VFD
Function
Name
code
power outage the power off and then power on.
Waiting time of
P01.22
restart after
power outage
Start delay
P01.23
time
Delay time of
P01.24
the stop
speed
0Hz output
P01.25
selection
P02 Group Motor 1
P02.00
Motor type 1
Rated power
P02.01
asynchronous
motor 1
Detailed instruction of parameters
0: Ddisable
1: Enable, if the starting need is met, the VFD will
run automatically after waiting for the time defined
by P01.22.
The function determines the waiting time before
the automatic running of the VFD when powering
off and then powering on.
Output frequency
Running Power off
Setting range: 0.0–3600.0s (valid when
P01.21=1)
The function determines the brake release after
the running command is given, and the VFD is in
a stand-by state and wait for the delay time set by
P01.23
Setting range: 0.0–60.0s
Setting range: 0.0–100.0 s
Select the output mode at 0Hz.
0: Output without voltage
1: Output with voltage
2: Output at DC braking current at stopping
0: Asynchronous motor
1: Synchronous motor
Note: Switch the current motor by the switching
channel of P08.31.
of
0.1–3000.0kW
t1=P01.22
t2=P01.23
t1
t2
Running
Power on
Set the parameters of
the controlled AM.
In
order
to
control performance, set
53
Function parameters
Default
Modify
value
1.0s
t
0.0s
0.0s
0
0
Depend
on
ensure
model
○
○
○
○
◎
◎