Goodrive300 Series VFD
Code
Fault
Inverter unit W
OUt3
phase
protection
Accelerating
OV1
overvoltage
Decelerating
OV2
overvoltage
Constant
OV3
overvoltage
Accelerating
OC1
overcurrent
Decelerating
OC2
overcurrent
Constant
OC3
overcurrent
Bus
UV
undervoltage
fault
OL1
Motor overload
OL2
VFD overload
Cause
wires is not good
Short-to-ground occurs.
The input voltage is abnormal
There
is
large
feedback
No braking components
Braking energy is not open
The
acceleration
deceleration is too fast
The voltage of the grid is too
low
The power of the VFD is too
low
The load transients or is
abnormal
The
grounding
circuited or the output is phase
loss
There
is
strong
interference
The
overvoltage
protection is not open
The voltage of the grid is too
low
overvoltage
The
protection is not open
The voltage of the grid is too
low
The rated current of the motor
is not correctly set
The
motor
stall
transients is too strong
The acceleration is too fast
190
Check the input power
Check if the DEC time of the load
is too short or the VFD starts
during the rotation of the motor or
energy
it needs to increase the energy
consumption components
Install
components
Check the setting of related
function codes
or
Increase the ACC/DEC time
Check the input power
Select the VFD with a larger
power
Check if the load is short circuited
(the grounding short circuited or the
wire short circuited) or the rotation is
is
short
not smooth
Check the output configuration.
Check
external
interference
Check the setting of related
stall
function codes
Check the input power of the grid
Check the setting of related
stall
function codes
Check the power of the grid
Reset the rated current of the
motor
Check the load and adjust the
or
load
torque lift
Increase the ACC time
Fault tracking
Solution
the
dynamic
braking
if
there
is
strong