Goodrive300 Series VFD
the password freely and the VFD will work as the last setting one. When P07.00 is set to 0, the
password can be canceled. If P07.00 is not 0 during powering on, then the parameter is protected by
the password. When modify the parameters by serial communication, the function of the password
follows the above rules, too.
Function
Name
code
P00 Group Basic function group
Speed control
P00.00
mode
Running
P00.01
command
channel
Detailed instruction of parameters
0: Sensorless vector control mode 0 (apply to AM
and SM)
No need to install encoders. It is suitable in cases
with low frequency, big torque and high speed
control accuracy for accurate speed and torque
control. Compared to mode 1, this mode is more
suitable for medium and small power.
1: Sensorless vector control mode 1 (applying to
AM)
No need to install encoders. It is suitable in cases
with high speed control accuracy for accurate
speed and torque control at all power ratings.
2: SVPWM control
No need to install encoders. It can improve the
control accuracy with the advantages of stable
operation, valid low-frequency torque boost and
current vibration suppression and the functions of
slip compensation and voltage adjustment.
Note: AM: Asynchronous motor,
SM: Synchronous motor;
Motor parameter autotuning must be performed
on the VFD first when the vector mode is used.
Select the run command channel of the VFD.
The control command of the VFD includes:
start-up, stop, forward, reverse, jogging and fault
reset.
0: Keypad ("LOCAL/REMOT" light off)
Carry out the command control by RUN,
STOP/RST on the keypad.
Set the multi-function key
FWD/REVC shifting function (P07.02=3) to
change the running direction; press RUN and
41
Function parameters
Default
value
QUICK/JOG
to
Modify
1
◎
0
○