Goodrive300 Series VFD
Function
Name
code
protection
coefficient
Correction
P02.28
coefficient of
motor 1 power
Parameter
P02.29
display of
motor 1
P03 Group
Vector control
Speed loop
P03.00
proportional
gain 1
Speed loop
P03.01
integral time 1
Detailed instruction of parameters
output current of the VFD and K is the motor
protection coefficient.
The smaller K is, the greater M is, and the more
likely protection is implemented.
When M=116%, protection is performed after
motor overload lasts for 1 hour; when M=150%,
protection is performed after motor overload lasts
for 12 minutes; when M=180%, protection is
performed after motor overload lasts for 5
minutes; when M=200%, protection is performed
after motor overload lasts for 60 seconds; and
when M ≥
400%, protection is performed
immediately.
Time (min)
60
12
5
1
116%
Setting range: 20.0%–120.0%
Correct the power displaying of motor 1.
Only impact the displaying value other than the
control performance of the VFD.
Setting range: 0.00–3.00
0: Display according to the motor type
1: Display all
The parameters P03.00–P03.05 only apply to
vector control mode. Below the switching
frequency 1 (P03.02), the speed loop PI
parameters are: P03.00 and P03.01. Above the
switching frequency 2 (P03.05), the speed loop PI
59
Motor overload
multiple
150% 180%
200%
Function parameters
Default
Modify
value
1.00
●
0
●
20.0
○
0.200s
○