12 ERROR CODE LISTS
Error
Details
code
code
Name
Read device data
from CPU shared
16421
memory (MULTR)
execution error
Write device data to
intelligent function
16422
module (TO)
execution error
Read device data
from intelligent
16423
function module
(FROM) execution
error
Error factor
Description
• Number of words (n) to be read is outside
the range of 1 to 256.
• The CPU shared memory first address
(S2) of the data which it will be read is
outside the range (000H to FFFH) of the
CPU shared memory address.
• The CPU shared memory first address
(S2) of the data which it will be read +
number of words (n) to be read is outside
the range (000H to FFFH) of the CPU
shared memory address.
• Start device No. (D) which stores the
reading data + number of words (n) to be
read is outside the device range.
• Except 3E0H/3E1H/3E2H/3E3H is set at
(S1).
• The CPU which reads is resetting.
• The errors are detected in the CPU which
read.
• (D) is a bit device and the device number
is not a multiple of 16.
• PX/PY is set in (D) to (D)+(n-1).
• Number of words (n) to be written is
outside the range of 1 to 256.
• Motion CPU cannot communicate with
intelligent function module at the
instruction execution.
• Abnormalities of the intelligent function
module were detected at the instruction
execution.
• I/O No.s specified with (D1) differ from the
intelligent function module controlled by
the self CPU.
• The address specified with (D2) is outside
the buffer memory range.
• Start device No. (S) which writing data are
stored + number of words (n) to be written
is outside the device range.
• (S) is a bit device and the device number
is not a multiple of 16.
• PX/PY is set in (S) to (S)+(n-1).
• Number of words (n) to be read is outside
the range of 1 to 256.
• Motion CPU cannot communicate with
intelligent function module at the
instruction execution.
• Abnormalities of the intelligent function
module were detected at the instruction
execution.
• I/O No.s specified with (S1) differ from the
intelligent function module controlled by
the self CPU.
• The address specified with (S2) is outside
the range buffer memory.
• Start device No. (D) which stores the
reading data + number of words (n) to be
read is outside the device range.
• (D) is a bit device and the device number
is not a multiple of 16.
• PX/PY is set in (D) to (D)+(n-1).
12 - 18
Error Processing
• Correct the program so that the number of
words (n) to be read is within the range of 1
to 256.
• Correct the program so that the CPU
shared memory first address (S2) of the
data which it will be read is within the
device range of CPU shared memory
address.
• Correct the program so that the CPU
shared memory first address (S2) of the
data which it will be read + number of
words (n) to be read is within the range of
CPU shared memory address.
• Correct the program so that start device
No. (D) which stores the reading data +
number of words (n) to be read is within the
device range.
• Correct the program so that
3E0H/3E1H/3E2H/3E3H is set at (S1).
• Check that the resetting flag (SM240 to
SM243) is OFF, then correct the program to
execute the MULTR instruction.
• If the errors are detected in the CPU which
read, exchange the CPU.
• When (D) is a bit device, set the device
number to be multiple of 16.
• When (D) is a bit device, do not set PX/PY.
• Correct the program so that the number of
words (n) to be written is within the range of
1 to 256.
The block processing
• Replace the intelligent function module if
in execution is
there is a fault.
stopped and the next
• Correct the program so that the first I/O
block is executed.
No.s specified with (D1) is intelligent
function module controlled by the self CPU.
• Correct the program so that the address
specified with (D2) is within the buffer
memory range.
• Correct the program so that start device No.
(S) which writing data are stored + number
of words (n) to be written is within the
device range.
• When (S) is a bit device, set the device
number to be multiple of 16.
• When (S) is a bit device, do not set PX/PY.
• Correct the program so that the number of
words (n) to be read is within the range of 1
to 256.
• Replace the intelligent function module if
there is a fault.
• Correct the program so that the first I/O
No.s specified with (S1) is intelligent
function module controlled by the self CPU.
• Correct the program so that the address
specified with (S2) is within the buffer
memory range.
• Correct the program so that start device No.
(D) which stores the reading data + number
of words(n) to be read is within the device
range.
• When (D) is a bit device, set the device
number to be multiple of 16.
• When (D) is a bit device, do not set PX/PY.
Corrective Action