Mitsubishi Electric Melsec Q Series Programming Manual page 480

Motion controller (sv13/sv22)
Hide thumbs Also See for Melsec Q Series:
Table of Contents

Advertisement

12 ERROR CODE LISTS
Error
Details
code
code
Name
16-bit integer type
16412
scaling (SCL)
execution error
32-bit integer type
16413
scaling (DSCL)
execution error
1
2
3
Cam data read
16414
(CAMRD) execution
error
4
5
6
7
Error factor
Description
• (S1) is outside the range of 0 to 3.
• The device number of (S3) is odd-
numbered.
• (S3) to (S3) + (2N + 1) is outside the
device range.
• The number of points is outside the range
of 2 to 4000.
• In the sequential search ((S1) is 0 or 1),
the points corresponding to the input
values (for positive conversion: X
/for inverse conversion: Y
to Y
1
0
not in ascending order.
• The conversion results are outside the
range of the data type (D).
• (S1) is outside the range of 0 to 3.
• The device numbers of (S2), (S3), and (D)
are odd-numbered.
• (S3) to (S3) + (4N + 1) is outside the
device range.
• The number of points is outside the range
of 2 to 2000.
• In the sequential search ((S1) is 0 or 1),
the points corresponding to the input
values (for positive conversion: X
/for inverse conversion: Y
to Y
1
0
not in ascending order.
• The conversion results are outside the
range of the data type (D).
Cam No. specified by (S1) is outside the
range of 1 to 256.
Cam data which No. is specified by (S1)
does not exist in cam open area.
• In the stroke ratio data format cam, the
cam data first position specified by (S2) is
outside the range of 1 to cam resolution.
• In the coordinate data format cam, the
cam data first position specified by (S2) is
outside the range of 0 to (coordinate
number - 1).
• In the stroke ratio data format cam, cam
data operation points is outside the range
of 1 to 4096.
• In the coordinate data format cam, cam
data operation points is outside the range
of 1 to 2048.
The end device number which stores the
cam data is outside the range.
The first number of the storage device for
(D) cam data is not even-numbered.
Read the cam data with "Read/write
protection" password set.
12 - 13
Error Processing
to X
0
N-
) are
N-1
to X
0
N-
The block processing
) are
N-1
on executing is
stopped and the next
block is executed.
Corrective Action
• Correct the program so that the (S1) is
within the range of 0 to 3.
• Correct the program so that the (S3) is
even-numbered device.
• Correct the program so that the devices
from (S3) to (S3) + (2N + 1) are within the
range.
• Correct the program so that the number of
points is within the range of 2 to 4000.
• Correct the program so that the points
corresponding to the input values (for
positive conversion: X
to X
/for inverse
0
N-1
conversion: Y
to Y
) increases
0
N-1
monotonically.
• Correct the program so that the conversion
results are within the data type (D).
• Correct the program so that the (S1) is
within the range of 0 to 3.
• Correct the program so that the (S2), (S3),
and (D) are even-numbered devices.
• Correct the program so that the devices
from (S3) to (S3) + (4N + 1) are within the
range.
• Correct the program so that the number of
points is within the range of 2 to 2000.
• Correct the program so that the points
corresponding to the input values (for
positive conversion: X
to X
/for inverse
0
N-1
conversion: Y
to Y
) increases
0
N-1
monotonically.
• Correct the program so that the conversion
results are within the data type (D).
Correct the program so that the cam No. is
within the range of 1 to 256.
Correct the program to specify a cam No. in
which cam data exists.
• In the stroke ratio data format cam, correct
the program so that it is within the range of
1 to cam resolution.
• In the coordinate data format cam, correct
the program so that it is within the range of
0 to (coordinate number - 1).
• In the stroke ratio data format cam, correct
the program so that it is within the range of
1 to 4096.
• In the coordinate data format cam, correct
the program so that it is within the range of
1 to 2048.
Correct the operation points so that the end
device number which stores the cam data is
within the range.
Correct the program so that the device
number is an even-numbered.
Execute the cam data read operation after
the password is disabled.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents