12 ERROR CODE LISTS
Error
Details
code
code
Name
Operation (/)
16320
—
execution error
Remainder (%)
16321
—
execution error
Device set (SET)
16322
—
execution error
Device reset (RST)
16333
—
execution error
Device set (SET=)
16334
—
execution error
Device reset (RST=)
16335
—
execution error
Device output (DOUT)
16336
—
execution error
Device input (DIN)
16337
—
execution error
Bit device output
16338
—
(OUT=) execution
error
Direct specification 16
bit Multiple CPU area
16368
—
device for CPU No.1
(U3E0\G10000 to)
read error
Direct specification 32
bit Multiple CPU area
16369
—
device for CPU No.1
(U3E0\G10000 to)
read error
Direct specification 64
bit Multiple CPU area
16370
—
device for CPU No.1
(U3E0\G10000 to)
read error
Direct specification 16
bit Multiple CPU area
16371
—
device for CPU No.2
(U3E1\G10000 to)
read error
Direct specification 32
bit Multiple CPU area
16372
—
device for CPU No.2
(U3E1\G10000 to)
read error
Direct specification 64
bit Multiple CPU area
16373
—
device for CPU No.2
(U3E1\G10000 to)
read error
Direct specification 16
bit Multiple CPU area
16374
—
device for CPU No.3
(U3E2\G10000 to)
read error
Direct specification 32
bit Multiple CPU area
16375
—
device for CPU No.3
(U3E2\G10000 to)
read error
Error factor
Description
The divisor is 0.
• The device No. which indirectly specifies
(D) is illegal.
• (D) is a device which is write-disabled.
The device No. which indirectly specifies (D)
is illegal.
Multiple CPU area device number is outside
the range that set by the parameter.
12 - 11
Error Processing
Correct the program so that the divisor is
other than 0.
• Correct the program so that the device No.
which indirectly specifies (D) is proper.
• Correct the program to set a write-enabled
device at (D).
Correct the program so that the device No.
which indirectly specifies (D) is proper.
The block processing
on executing is
stopped and the next
block is executed.
Correct the program so that Multiple CPU
area device number is within the range set
in the parameter.
Corrective Action