Advertisement

5 OPERATION CONTROL PROGRAMS
[Errors]
[Program examples]
(4) (S2) is set in increments of 10ms.
When the setting is omitted, the timeout time is 10 seconds (same as setting
1000).
The process time is changed according to job contents in the vision system. Set
the timeout time according to the vision system and the job contents.
(1) An operation error will occur if:
• The (S1) data is outside the range of 1 to 32.
• The (S2) data is outside the range of 1 to 32767.
• The vision system which is used in the vision program specified with (S1) has
not been logged on.
• The vision system parameter setting (Refer to APPENDIX 3.2.) is different from
the setting on the vision system and the job.
• The tag specified with reading value cell or the spreadsheet data is not an
integer value.
• The current process is not completed when the specified timeout time has
elapsed.
(1) Program which executes the job of the vision program No.20
MVPST K20
5 - 134