[Errors]
(Note)
Complete status
(Error code)(H)
0010
2205
(Note)
Error code
4350
4351
4352
4353
4354
The abnormal completion in the case shown below, and the error code is stored in the
device specified with the complete status storage device (D2).
If the complete status storage device (D2) is omitted, an error is not detected and
operation becomes "No operation".
Instruction request to Motion CPU from PLC CPU exceeds the permissible
value.
Axis No. set by D(P).CHGT instruction is wrong.
The diagnostic error flag (SM0) is turned on an operation error in the case shown
below, and an error code is stored in the diagnostic error register (SD0).
The target CPU module specified is wrong.
(1) The reserved CPU is specified.
(2) The uninstalled CPU is specified.
(3) The first I/O number of the target CPU/16 (n1) is outside the range of
3E0H to 3E3H.
It cannot be executed to the specified target CPU module.
(1) The instruction name is wrong.
(2) The instruction unsupported by the target CPU module is specified.
The number of devices for instruction specified is wrong.
The device that cannot be used by the instruction specified is specified.
The character string that cannot be handled by the instruction specified is
specified.
Error factor
Error factor
3 - 48
Corrective action
Confirm a program,
and correct it to a
correct sequence
program.
(Note): 0000H (Normal)
Corrective action
Confirm a program,
and correct it to a
correct sequence
program.
(Note): 0 (Normal)