8.5.3.7

Controlled stop, EMERGENCY STOP category 1

The EMERGENCY OFF function for controlled shutdown stops the drive by means of a quick
stop process along a deceleration ramp that must be parameterized.
Note
The drive is stopped during controlled deceleration without braking modules with only a very
low % braking torque. Depending on the load machine, the ramp-down procedure may take a
long time.
Connections of the EMERGENCY STOP button
Most of the contacts of the EMERGENCY STOP button are integrated in the control circuit of
the circuit-breaker. The two remaining normally-closed contacts of the EMERGENCY STOP
button are situated on the terminal block.
EMERGENCY
STOP button
=.LA-S31:11-12
=.LA-S31:21-22
=.LA-S31:31-32
=.LA-S31:51-52
=.LA-S31:61-62
Max. connectable cross-section: 4 mm² (AWG 10)
You will find further information in the section "Circuit book" in your operating instructions.
8.6

Fault and system messages

8.6.1

External alarms and faults

With the optional terminal blocks TM15/TM31, there are 24 terminals. You can select the
following with SCOUT:
1. Any messages that should be displayed.
2. Protection devices that should be triggered.
The list of parameterized faults and alarms can be found in the List Manual in the "Faults and
alarms" section.
SINAMICS SM150 6SL3845-2NN41-8AD2
Operating Instructions Rev.201910281310 EXAMPLE
Where connected
=.LA-X11:9-10
Circuit breaker con‐
=.LA-X11:5-6
trol circuit
=.LA-X11:7-8
EMERGENCY STOP
=.LA-X51:1, 2
customer
Excitation equipment
=.LA-X51:3, 4
Operation
8.6 Fault and system messages
If jumpered STOP; if not jumpered
EMERGENCY OFF (produces an
instantaneous stop command on
the circuit-breaker)
121