Get Configuration - ABB STT04 Instruction Manual

Smart transmitter terminal
Table of Contents

Advertisement

OPERATING PROCEDURES

GET CONFIGURATION

Key
G E T
[nnnnnnnnnnnnnnnnnn]
C O N F IG
STORE THIS
CONFIGURATION?
E N TE R
→ YES
CONFIG ID TAGNAME
DEVICE MFR: ABB
E N TE R
CONFIG ID TAGNAME
E N TE R
MODE: DIGITAL
OUTPUT TYPE:
E N TE R
→ SQUARE ROOT
OUTPUT ACTION:
→ NORMAL
E N TE R
GET CONFIGURATION
4 - 8
Use the get configuration function key to view and save the configura-
tion of a connected field device. Get configuration requires that the
STT04 terminal be connected to a device.
NOTE: This procedure is similar for all device types. It is intended as
a general guide for this function. Variances occur based on device
type.
Display
SELECTED
CONFIGURATION
NO
TYPE: 600T
CHANNEL: 2
LINEAR
3/2 FLOW MODE
REVERSE
Comments
The name within the brackets is the working
configuration.
The option to save the configuration in the STT04
terminal internal memory is presented. When the
configuration is stored, exit the function by pressing
.
CLEAR
NOTE: A maximum of 100 configurations can be
stored in the STT04 terminal.
The device ID tag name and manufacturer is dis-
played for HART transmitters only.
Displays the 14 character ID tag name of the con-
nected device. The TYPE field displays the device
type. If ANALOG mode, the CHANNEL field will not
show.
Indicator points to the configured output type.
NOTE: Use
to return to any screen during
BACK
configuration.
Configured output action is displayed.