Configuration Via Fdt/Dtm Technology; Configuration Via Edd Technology; Configuration With The Handheld Terminal; Configuration Via The Lcd Display / Configuration Software With The Control Buttons - ABB TTF350 Operating Instructions Manual

Field mounted temperature transmitters
Hide thumbs Also See for TTF350:
Table of Contents

Advertisement

Configuration
7.2

Configuration via FDT/DTM technology

Configuration can be performed with any FDT network applications that are approved for use
with the DTM (e.g., Smart Vision). The bus can be connected via FSK modem as well as HART
+ USB, Profibus + remote I/O or HART Multiplexer.
7.3

Configuration via EDD technology

Configuration can also be performed with EDD master applications such as Siemens Simatic,
which is approved for use with EDD. In contrast to DTM configuration, EDD has process-
dependent, minor limitations such as configuration of a freestyle characteristic.
7.4

Configuration with the handheld terminal

The configuration with the handheld terminal normally takes place at the factory before the
installation of the transmitter in an industrial plant.
1. Open the housing of the head-mounted measuring inset.
2. Carefully clamp both test tips of the separate operating control on the contacts in the slotting
in front of the + and – connection terminals.
3. Be sure the test terminals are firmly seated.
4. The installation is to be realized according to the figure in the "Configuration types"
paragraph.
Important
The connection of the test tips is performed without polarity. Thus, it does not make a
difference which test tip is clamped to which + or – connection terminal.
The configuration of the transmitter via the HART protocol can also take place during the
normal operation.
7.5

Configuration via the LCD display / configuration software with the control buttons

During operation, the name of the measuring site of the flowmeter primary (tag) and the reading
are shown on the LCD display (see section 16).
Important
In contrast to the SmartVision software, the functionality of the transmitter with the LCD
display and the control buttons is only partially changeable.
The configuration of the transmitter parameters is described in the section "Configuration with
the LCD display and the control buttons" in this manual.