E N TE R
CALIBRATION
D - 10

METER VALUE ADJUSTMENT

Use this function to adjust the four to 20 milliampere output of the field
device using values from an external current meter. This method is
only valid for HART devices.
Display
NO
BENCH CALIB.
READY
Comments
This operation will cause a change in output not cor-
responding to the input. Be sure the control loop is in
manual.
Select YES.
Select D-TO-A ADJUST.
Select METER VALUE ENTRY.
Use the number keys to enter the current meter
reading.
Use the number keys to enter the current meter
reading.