TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF300-EN REV. G

10 Commissioning

General

In case of corresponding order the transmitter is ready for
operation after mounting and installation of the connections.
The parameters are set at the factory.
If not exclusively selected while ordering the profile HART 7, the
transmitter is delivered present with the profile HART 5. The
profile can be always switched to HART 7 via a miniature switch,
see Hardware settings on page 42.
The connected lines must be checked for firm seating. Only
firmly seated lines ensure full functionality.

Checks prior to commissioning

The following points must be checked before commissioning the
device:
Correct wiring in accordance with Electrical connections
on page 27.
The ambient conditions must correspond to the
information given on the name plate and in the data
sheet.

Communication

HART® Communication
Note
The HART® protocol is an unsecured protocol, as such the
intended application should be assessed to ensure that these
protocols are suitable before implementation.
Communication with the transmitter takes place using the HART
protocol. The communication signal is modulated onto both
wires of the signal line in accordance with the HART FSK 'Physical
Layer' specification.
The HART modem is connected at the signal line of the current
output via which power is also supplied via the power supply
unit.
The device is listed with the FieldComm Group.
1 Transmitter
2 Handheld terminal
3 HART® modem
4 PC with Asset Management Tool
Figure 32: Example for HART® connection
Manufacturer ID
Device ID
Profile
Configuration
Transmission signal

Operating modes

Point-to-point communication mode – standard (general
address 0)
Multidrop mode (addressing 1 to 15)
Burst Mode

Configuration options / tools

Driver-independent:
HMI LCD indicator with configuration function
Driver-dependent:
Device management / Asset management tools
FDT technology – via TTX300-DTM driver
(Asset Vision Basic / DAT200)
EDD – via TTX300 EDD driver
(Handheld terminal, Field Information Manager / FIM)
FDI technology – via TTX300 package
(Field Information Manager / FIM)

Diagnosis notice

Overrange- / underrange in accordance with NE 43
HART diagnosis
5 Grounding (optional)
6 Power supply unit (process
interface)
R
load resistance
B
(if necessary)
HART 5: 0x000B,
HART 7: 0x1A0B
HART 5.1 (can be switched to HART 7)
On device using LCD indicator
DTM, EDD, FDI (FIM)
BELL Standard 202
39