ABB STT04 Instruction Manual page 108

Smart transmitter terminal
Table of Contents

Advertisement

Key
Display
OUTPUT TYPE:
→ LINEAR
E N TE R
FUNC GENERATOR
OUTPUT ACTION:
→ NORMAL
E N TE R
REVERSE
DAMPING:
(0-32 SEC)
E N TE R
nn.nn SECS
LOWER RANGE VAL
nn.nn
E N TE R
UPPER RANGE VAL
nn.nn
INITIALIZE MODE:
→ LOW
E N TE R
HIGH
FAIL MODE:
→ LOW
E N TE R
HIGH
LAST
ENTER
SECONDARY UNITS
E N TE R
nnnnnn
SECONDARY L.R.
_nn.nn UNITS
E N TE R
SECONDARY U.R.
nn.nn UNITS
EQS TEMPERATURE TRANSMITTER
Select LINEAR.
If FUNC GENERATOR is selected, specify 5 input
and output points between 0 and 100%.
Refer to the Platinum Standard Series Smart Tem-
perature Transmitter EQS instruction for descrip-
tion.
Enter a value between 0 and 32. Refer to the Plati-
num Standard Series Smart Temperature Trans-
mitter EQS instruction for description.
Enter the lower range temperature value and press
. Input the upper range value.
ENTER
C
o
C
o
Select an initialization mode using the arrow keys.
Refer to the Platinum Standard Series Smart Tem-
perature Transmitter EQS instruction for descrip-
tion.
Select a fail mode using the arrow keys.
Refer to the Platinum Standard Series Smart Tem-
perature Transmitter EQS instruction for descrip-
tion.
Enter up to 6 characters. Use familiar units to
describe the output.
To select a character, press the key that has the
desired character. Continue to press the key until the
desired character appears. Use the right arrow key to
move to the next character. Use the left arrow key to
go back to the previous character. Press
when finished.
Input the lower range value and press
Input the upper range value.
Comments
CREATE/MODIFY CONFIGURATION
ENTER
.
ENTER
C - 3