ABB STT04 Instruction Manual page 16

Smart transmitter terminal
Table of Contents

Advertisement

Key
E N TE R
E N TE R
METER VALUE ADJUSTMENT
Use this function to adjust the four to 20 milliampere output of the field device using values from an external current
meter. This method is only valid for HART devices.
Key
C A LI-
B R ATE
E N TE R
E N TE R
E N TE R
Display
ADJUST TO 20 mA
THEN HIT ENTER
ID TAGNAME
READY
Display
OUTPUT WILL BE
AFFECTED! PROCEED?
NO
→ YES
CALIBRATION
SENSOR TRIM
→ D-TO-A ADJUST
PV BIAS
SET OUTPUT %
D/A CAL USING
UPDOWN ARROW KEYS
→ METER VALUE ENTRY
FACTORY DAC TRIM
ADDENDUM
Comments
Use the arrow keys to adjust the 20 mA signal.
Comments
This operation will cause a change in output not cor-
responding to the input. Be sure the control loop is in
manual.
Select YES .
Select D-TO-A ADJUST .
Select METER VALUE ENTRY .