Key
Display
LOW CALIB PRESSURE
nn.nn UNITS
E N TE R
HIGH CALIB PRESSURE
nn.nn UNITS
APPLY PRESSURE OF
nn.nn UNITS
E N TE R
THEN HIT ENTER
APPLY PRESSURE OF
nn.nn UNITS
E N TE R
THEN HIT ENTER
APPLY PRESSURE OF
nn.nn UNITS
E N TE R
THEN HIT ENTER
ADJUST TO 4 mA
E N TE R
THEN HIT ENTER
ADJUST TO 20 mA
E N TE R
THEN HIT ENTER
ID TAGNAME
E N TE R
READY
BCN PRESSURE TRANSMITTER
Comments
Enter the low calibration pressure using the number
keypad. Press
. Then enter the high calibra-
ENTER
tion pressure.
Apply the low range value to the input of transmitter
as specified earlier.
Apply the high range value to the input of transmitter
as specified earlier.
Apply the middle range value. This value is calcu-
lated by STT04 terminal using low and high values.
If configured digitally this adjust selection does not
appear. Adjust transmitter output using up and down
arrow keys.
NOTE: When increasing or decreasing the mA sig-
nal, the increments of change increase with succes-
sive depressions until the maximum level of change
is reached. By changing direction the smallest incre-
ment of change returns. This technique speeds up
the process without affecting fine adjustment.
Adjust the transmitter output using up and down
arrow keys.
CALIBRATION
G - 7