TBN580 TRANSMITTER

Bench Calibration Temperature

Key
OUTPUT WILL BE
AFFECTED! PROCEED?
C A LI-
B R ATE
→ YES
CALIBRATION
E N TE R
→ BENCH CAL TEMP
ENTER FIXED
PROCESS TEMP
E N TE R
E N TE R
ID TAGNAME
E N TE R
CALIBRATION
K - 10
The following procedure steps through the bench calibration of the
temperature.
Display
NO
PROCESS CAL
BENCH CAL pH
nnn.n° UNITS
CHANGE TEMP
OF PROCESS?
nnn.n° UNITS
READY
Comments
This operation will cause a change in output not cor-
responding to the input. Be sure the control loop is in
manual.
Select YES.
Select BENCH CAL TEMP.
If in TEMP COMP TYPE, MANUAL or NONE is
selected during configuration, this screen will not
appear, otherwise the next screen, CHANGE TEMP
OF PROCESS? appears. Default is 25°C.
The value displayed is the temperature of the pro-
cess (interior of sensor).
NOTE: If a new temperature value is entered, this
change will affect the calibration of temperature.