Calibration; Input A/D; D-To-A Adjust; Calibration Flowchart (As800 - ABB STT04 Instruction Manual

Smart transmitter terminal
Table of Contents

Advertisement

CALIBRATION

This section details the AS800 pressure transmitter calibration func-
tions using an STT04 terminal. There are four types of calibration
functions:

Input A/D

D-to-A adjust (Analog Mode only)
Zero Trim
Temperature
NOTES:
1.
When calibrating, a field device must be connected to the
STT04 terminal.
2.
To change calibration or configuration parameters of a field
device that is connected to an IMFBS01 module, the transmitter
must be taken off-line. This is done at the INFI 90 OPEN console.
Refer to Figure
P-2
for an overview of the calibration functions.
Figure P-2. Calibration Flowchart (AS800)
AS800 PRESSURE TRANSMITTER
CALIBRATION
P - 5