Table 5-2. STT04 Error Messages for ABB FSK Devices
Message
VALUES OUT OF
ACCEPTABLE RANGE
FOR FIELD DEVICE
VALVE STUCK
Positioner Valve has not moved for
OPTION NOT
INSTALLED
Affected
Probable Cause
Device
All FSK
Value specified in the con-
figuration is below the
limit.
over two minutes.
XM/SM/
The current configuration
XE
is calling to use the empty
pipe detector which
requires an optional
board.
(continued)
Corrective Action
Refer to the appropriate product instruc-
tion for the value limits.
Check 4 to 20 mA input.
Check valve.
Check 4 to 20 mA input.
Add empty pipe detector option, or turn
empty pipe detection off in the
configuration.