SMART POSITIONER

Output D-to-A Calibration

Key
OUTPUT WILL BE
AFFECTED! PROCEED?
C A LI-
B R ATE
→ YES
→ OUTPUT D/A CAL
E N TE R
E N TE R
ADJUST TO 20 mA
E N TE R
ID TAGNAME
E N TE R
CALIBRATION
A - 6
The D-TO-A ADJUST selection is only present when you are in the
ANALOG communication mode, specified in the configuration proce-
dure. This selection allows you to adjust the four to 20 milliampere
output of the field device.
NOTE: Analog board must be installed for this function.
Display
NO
INPUT A/D CAL
MAN POSITION CAL
AUTO POSITION CAL
ADJUST TO 4mA
THEN HIT ENTER
THEN HIT ENTER
READY
Comments
Select OUTPUT D/A CAL.
Use the up and down arrow keys to adjust the 4 mA
signal.
When increasing or decreasing the mA signal, the
increments of change increase with successive
depressions until the maximum level of change is
reached. By changing direction you will return to the
smallest increment of change. This adjustment tech-
nique speeds up the adjustment process without
affecting fine adjustment.
Use the up and down arrow keys to adjust the 20 mA
signal.
NOTE: Refer to Positioner instruction for details on
the calibrations.