TROUBLESHOOTING
Table 5-2. STT04 Error Messages for ABB FSK Devices
Message
CONFIG TAGNAME
ALREADY EXISTS
DAMAGED
CELL OR
CHARACTERIZATION
BOARD
DEVIATION
ALARM
DEVICE IN WRITE
PROTECT MODE
DYNAMIC
TEMPERATURE
MEASUREMENT
FAILURE
ELECTRONICS
TEMPERATURE
MEASUREMENT
FAILURE
ELECTRONIC
TEMPERATURE
OUT OF RANGE
EMPTY PIPE
ERROR! ATTEMPT TO
CONFIGURE
DUPLICATE
ADDRESS
ERROR!
DEVICE TYPE
AND CONFIGURATION
NOT COMPATIBLE
FIELD DEVICE CAN'T
EXECUTE
COMMAND:
COMMAND CONFLICT
ERROR MESSAGES
5 - 6
Affected
Probable Cause
Device
All FSK
Attempted to copy a
configuration to a car-
tridge or field device
where it already exists.
PTS
Characterization board or
cell is damaged.
AVS
Deviation has been
greater than the alarm
setting for two minutes.
STT
Device is write protected.
PTS
Dynamic temperature
input exceeded limits set
at factory.
NOTE: The temperature of the
high side of the cell with respect to
the low side of a PTS.
EQS
Hardware failure of
PTS
on-board temperature
sensor.
PTS
Electronics temperature is
outside the factory speci-
fied limit.
XM/SM/
The flowmeter is empty.
XE
All FSK
Attempt was made to
assign an analog mode
transmitter an address on
FBS module.
Attempt was made to
assign a digital mode
transmitter to an occu-
pied FBS address.
All FSK
The configuration type
(i.e., PTS) does not match
the device type (i.e.,
BCN).
BCN
Commands were sent by
EQN
STT terminal in the wrong
TBN
order. Verify IMFBS01 is
off-line if STT terminal is
in use.
(continued)
Corrective Action
Erase old configuration before copying
new one. Refer to
OPERATING PROCE-
DURES
in Section 4.
Replace amplifier assembly. Refer to
repair/replacement section of the appro-
priate product instruction.
Replace cell/characterization board.
Refer to repair/replacement section of the
appropriate product instruction.
Check valve.
Check PID tuning.
Change mode of device before trying to
configure or calibrate.
Output may no longer be accurate.
Remove source of temperature shift.
Replace amplifier assembly. Refer to
repair/replacement section of the appro-
priate product instruction.
Remove the source of the temperature
extreme.
Allow process to fill flow tube.
Be sure transmitter is in the correct mode
(analog or digital). Use
VIEW
mode. Refer to
OPERATING PROCE-
DURES
in Section 4 for details.
Assign transmitter to an unoccupied
address or channel number of FBS
module.
Select a device that is compatible with
the configuration.
Try command again.
to verify