Table 5-1. STT04 Error Messages for HART Devices
Affected
Message
Device
TEMP SLOPE
WARNING
USER TEMP HI/LO
ALARM
Table 5-2. STT04 Error Messages for ABB FSK Devices
Affected
Message
CALIBRATION
REQUIRED
CANNOT SAVE,
CONFIGURATION
TOO LARGE
CELL
CHARACTERIZATION
BOARD
EEPROM FAILURE
CELL
TEMPERATURE
OVER USER ALARM
CELL
TEMPERATURE
UNDER USER ALARM
CELL TEMPERATURE
OVER LIMIT
CELL TEMPERATURE
UNDER LIMIT
COMMAND ABORTED
COMMUNICATION
ERROR
Probable Cause
TB82
High or low temperature
slope
EBTH
Cell temperature over/
under user alarm limit.
Probable Cause
Device
PTS
Cell has not been
calibrated with present
amplifier assembly.
EQS
Field device needs to be
calibrated.
STT
Transmitter type not sup-
ported by STT terminal
revision level.
PTS
Damage to cell
characterization board.
PTS
Cell temperature over/
EQS
under user alarm limit.
PTS
Cell temperature input is
over/under factory speci-
fied limits.
STT
Cancel key pressed
before function was com-
pleted.
STT
Noisy signal.
TROUBLESHOOTING
(continued)
Corrective Action
Verify sensor wiring connections and
inspect cable for shorts. Remove all poten-
tial shorts to ground, conduit or metals.
Verify that sensor had 10 to 15 min. to accli-
mate to temperature environment to which it
was calibrated.
Disconnect temperature compensator leads
from transmitter and measure resistance.
Replace sensor with spare when transmitter
does not accept calibration values.
Correct temperature problem.
Change alarm value. Refer to configuration
procedures for
EBTH TEMPERATURE
TRANSMITTER
in Appendix B.
Corrective Action
Calibrate the field device. Refer to the
calibration section of the appropriate PTS
pressure transmitter instruction.
Calibrate the field device. Refer to the
calibration section of the appropriate
EQS temperature transmitter instruction.
Consult ABB to obtain latest STT terminal
revision.
Turn the STT terminal off and then on. If
error still exists, replace cell (refer to
repair/ replacement section of the appro-
priate product instruction for procedure).
Correct temperature problem.
Change alarm value. Refer to configura-
tion procedures for
EQS TEMPERA-
TURE TRANSMITTER
in Appendix C or
PTS PRESSURE TRANSMITTER
Appendix E.
Remove the source of temperature
extreme.
Try function again.
Check terminal wiring and eliminate
source of noise.
ERROR MESSAGES