PV Bias
The PV Bias calibration procedure allows you to align the "zero" of the process with the "zero" reading of the
transmitter. This may be done in one of two ways:
Apply a pressure that corresponds to the desired zero offset or bias [SET PV ZERO]
To scale to a value different from zero, calculate the offset or biasand apply it to the 600T EN [SET PV VAL]
Key
C A LI-
B R ATE
E N TE R
Display
4 mA CALIBRATION:
ENTER METER VALUE
n.nnnn
20 mA CALIBRATION:
ENTER METER VALUE
nn.nnnn
ID TAGNAME
READY
Display
OUTPUT WILL BE
AFFECTED! PROCEED?
NO
→ YES
ADDENDUM
Comments
Use the number keys to enter the current meter
reading.
Use the number keys to enter the current meter
reading.
Comments
This operation will cause a change in output not cor-
responding to the input. Be sure the control loop is in
manual.
Select YES .
15