Calibration; Bench Calibration; D-To-A Adjust - ABB STT04 Instruction Manual

Smart transmitter terminal
Table of Contents

Advertisement

EQN TEMPERATURE TRANSMITTER
Key
FAIL MODE:
→ LOW
E N TE R
ENTER
SECONDARY UNITS
E N TE R
_nnnnnn
SECONDARY L.R.
E N TE R
SECONDARY U.R.
STORE THIS
CONFIGURATION
E N TE R
→ YES
ID TAGNAME
E N TE R

CALIBRATION

CALIBRATION
H - 4
Display
HIGH
LAST
_nn.nn UNITS
nn.nn UNITS
NO
READY
This section details the EQN temperature transmitter calibration func-
tions of the STT04 terminal. There are two types of calibration func-
tions:

Bench calibration.

D-to-A adjust.

NOTES:
1.
When calibrating, a field device must be connected to the
STT04 terminal.
2.
To change calibration or configuration parameters of a field
device that is connected to an IMFBS01 module, the transmitter
must be taken off-line. This is done at the INFI 90 OPEN console.
Comments
Refer to the Smart Electronic Temperature Trans-
mitter EQN instruction for description.
Enter up to 6 characters. Use familiar units to
describe the output.
To select a character, press the key that has the
desired character. Continue to press the key until the
desired character appears. Use the right arrow key to
move to the next character. Use the left arrow key to
go back to the previous character. Press
when finished.
Input the lower range value and press
the upper range value.
The Configuration ID tag name just configured will be
in the upper left corner if the configuration is saved. It
becomes the working configuration.
ENTER
. Input
ENTER