Meter Value Adjustment - ABB STT04 Instruction Manual

Smart transmitter terminal
Table of Contents

Advertisement

AS800 PRESSURE TRANSMITTER
Key
ADJUST TO 20 mA
E N TE R
THEN HIT ENTER
ID TAGNAME
E N TE R
Key
OUTPUT WILL BE
AFFECTED! PROCEED?
C A LI-
B R ATE
→ YES
CALIBRATION
→ D-TO-A ADJUST
E N TE R
D/A CAL USING
UPDOWN ARROW KEYS
E N TE R
→METER VALUE ENTRY
CALIBRATION
P - 8
Display
READY

METER VALUE ADJUSTMENT

Use this function to adjust the four to 20 milliampere output of the field
device using values from an external current meter. This method is
only valid for HART devices.
Display
NO
BENCH CALIB.
Comments
Use the arrow keys to adjust the 20 mA signal.
Comments
This operation will cause a change in output not cor-
responding to the input. Be sure the control loop is in
manual.
Select YES.
Select D-TO-A ADJUST.
Select METER VALUE ENTRY.