Meter Value Adjustment - ABB STT04 Instruction Manual

Smart transmitter terminal
Table of Contents

Advertisement

Key
Display
ADJUST TO 20 mA
E N TE R
THEN HIT ENTER
ID TAGNAME
E N TE R
READY

METER VALUE ADJUSTMENT

Use this function to adjust the four to 20 milliampere output of the field
device using values from an external current meter. This method is
only valid for HART devices.
Key
Display
OUTPUT WILL BE
AFFECTED! PROCEED?
C A LI-
NO
B R ATE
→ YES
E N TE R
CALIBRATION
SENSOR TRIM
→ D-TO-A ADJUST
PV BIAS
SET OUTPUT %
E N TE R
D/A CAL USING
UPDOWN ARROW
E N TE R
KEYS
→ METER VALUE ENTRY
600T & 600T EN PRESSURE TRANSMITTER
Comments
Use the arrow keys to adjust the 20 mA signal.
Comments
This operation will cause a change in output not cor-
responding to the input. Be sure the control loop is in
manual.
Select YES.
Select D-TO-A ADJUST.
Select METER VALUE ENTRY.
CALIBRATION
Q - 23