Set Output - ABB STT04 Instruction Manual

Smart transmitter terminal
Table of Contents

Advertisement

600T & 600T EN PRESSURE TRANSMITTER

Set Output %

Key
OUTPUT WILL BE
AFFECTED! PROCEED?
C A LI-
NO
B R ATE
→ YES
E N TE R
CALIBRATION
SENSOR TRIM
D-TO-A ADJUST
PV BIAS
→ SET OUTPUT %
[ 3 TIMES ]
E N TE R
SET OUTPUT %
→ LOW
E N TE R
HIGH
OP %: nnn.nn %
PV VAL:
E N TE R
Hit ENTER to set OP%
ENTER NEW VALUE
E N TE R
ID TAGNAME
E N TE R
CALIBRATION
Q - 26
Display
This operation will cause a change in output not cor-
responding to the input. Be sure the control loop is in
manual.
Select YES.
Select SET OUTPUT %.
If digitally configured, the D-TO-A ADJUST selection
will not appear.
Select LOW and press
HIGH selection is identical).
Display indicates present data.
value units
Enter LOW value,
value %
READY
Comments
. (Procedure for
ENTER
ENTER
.