EQN TEMPERATURE TRANSMITTER
Key
E N TE R
E N TE R
ENTER TRANSMITTER
AMBIENT TEMP.
E N TE R
ADJUST TO 4 mA
E N TE R
THEN HIT ENTER
ADJUST TO 20 mA
E N TE R
THEN HIT ENTER
ID TAGNAME
E N TE R
CALIBRATION
H - 6
Display
APPLY 0 mV
SIGNAL
THEN HIT ENTER
APPLY 25 mV
SIGNAL
THEN HIT ENTER
nn.nn C
READY
Comments
Apply 0 mV to the transmitter.
Apply 25 mV to the transmitter.
Enter the field device ambient temperature in
degrees Celsius using the number keypad. The sur-
rounding room temperature can be used for this tem-
perature value.
Adjust the transmitter output using the up and down
arrow keys.
Adjust the transmitter output using the up and down
arrow keys.
Bench calibration is complete.