Static Trim - ABB STT04 Instruction Manual

Smart transmitter terminal
Table of Contents

Advertisement

Key
OUTPUT WILL BE
AFFECTED! PROCEED?
C A LI-
B R ATE
NO
→ YES
E N TE R
→ SENSOR TRIM
D-TO-A ADJUST
E N TE R
PV BIAS
SET OUTPUT %
FULL TRIM
ZERO TRIM
FACTORY TRIM

→ STATIC TRIM

[ 3 TIMES ]
E N TE R
STATIC PRESSURE
value units
E N TE R
PRESS ENTER
TO MODIFY
STATIC PRESSURE
E N TE R
value units
ID TAGNAME
E N TE R
600T & 600T EN PRESSURE TRANSMITTER
STATIC TRIM
Use this option if the instrument is to be statically calibrated using a
known pressure.
Display
This operation will cause a change in output not cor-
responding to the input. Be sure the control loop is in
manual.
Select YES.
Select SENSOR TRIM, or select calibration option
with down-arrow key and refer to the appropriate
section. Press
Select STATIC TRIM.
Display shows the value of the pressure measured
by the 600T EN transmitter.
Enter the value of the actual static pressure using the
number keys.
READY
Comments
ENTER
when done.
CALIBRATION
Q - 21