B Parameter List
No.
Name
Number of Run Commands
o4-13
Counter Initialization
◆ q: DriveWorksEZ Parameters
No.
Name
q1-01 to q6-
DriveWorksEZ Parameters
07
◆ r: DriveWorksEZ Connection Parameters
No.
Name
DriveWorksEZ Connection
r1-01 to
Parameters 1 to 20 (upper/
r1-40
lower)
◆ T: Motor Tuning
Enter data into the following parameters to tune the motor and drive for optimal performance
■
T1: Induction Motor Auto-Tuning
No.
Name
T1-00
Motor 1 / Motor 2 Selection
T1-01
Auto-Tuning Mode Selection
<37>
T1-02
Motor Rated Power
T1-03
Motor Rated Voltage
<18>
T1-04
Motor Rated Current
T1-05
Motor Base Frequency
T1-06
Number of Motor Poles
T1-07
Motor Base Speed
PG Number of Pulses Per
T1-08
Revolution
172
0: Number of Run commands counter is not reset when the drive is initialized
(A1-03).
1: Number of Run commands counter is reset when the drive is initialized (A1-
03).
Reserved for DriveWorksEZ
DriveWorksEZ Connection Parameters 1 to 20 (upper/lower)
1: Motor 1 (sets E1-
, E2-
2: Motor 2 (sets E3-
, E4-
0: Rotational Auto-Tuning
1: Stationary Auto-Tuning 1
2: Stationary Auto-Tuning for Line-to-Line Resistance
3: Rotational Auto-Tuning for V/f Control (necessary for Energy Savings and
Speed Estimation Speed Search)
4: Stationary Auto-Tuning 2
8: Inertia Tuning (perform Rotational Auto-Tuning prior to Inertia Tuning)
9: ASR Gain Tuning (perform Rotational Auto-Tuning prior to ASR Gain Auto-
Tuning)
Sets the motor rated power as specified on the motor nameplate.
Note: Use the following formula to convert horsepower into kilowatts: kW =
HP x 0.746.
Set the motor rated voltage as specified on the motor nameplate.
Sets the motor rated current as specified on the motor nameplate.
Sets the rated frequency of the motor as specified on the motor nameplate.
Sets the number of motor poles as specified on the motor nameplate.
Sets the rated speed of the motor as specified on the motor nameplate.
Set the number of pulses per revolution for the PG being used (pulse generator
or encoder).
YASKAWA ELECTRIC TOEP C710616 21C YASKAWA AC Drive - A1000 Quick Start Guide
Description
Description
Description
Description
)
)
Setting
Default: 0
Min: 0
Max: 1
Setting
Refer to Help in the
DWEZ software.
Setting
Default: 0
Min: 0
Max: FFFFH
Setting
Default: 1
Min: 1
Max: 2
Default: 0
Min: 0
Max: 4, 8, 9
<10>
Default:
<6>
Min: 0.00 kW
Max: 650.00 kW
Default: 200.0 V
Min: 0.0 V
Max: 255.0 V
Default:
<6>
Min: 10% of drive
rated current
Max: 200% of drive
rated current
Default:
<46>
Min: 0.0 Hz
Max: 400.0 Hz
Default: 4
Min: 2
Max: 48
Default:
<47>
Min: 0 r/min
Max: 24000 r/min
Default:
<45>
Min: 0 ppr
Max: 60000 ppr