Connecting The Io Module To Safety Switching Devices Or Safety Modules; General Structure; Figure 12: Potential Group For Safety Related Applications - WAGO -I/O-SYSTEM 750 Manual

4-channel digital output module 24 vdc; 2-conductor connection; short-circuit-protected; highside switching
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
Applications
750-531 4DO 24V DC 0.5A/ 2-conductor
Pos : 82.6 /Serie 750 (WAGO-I/O-SYST EM)/Eins atz in sicherheitsg erichteten Anwendung en/Allgemeiner Aufbau ei ner Potenti algruppe - r üc kwir kungsfr eie Vari anten @ 6\mod_1258973074755_21.doc x @ 44664 @ 23 @ 1
7.2
Connecting the IO Module to Safety Switching
Devices or Safety Modules
7.2.1

General Structure

When using the interference-free variant ".../xxx-8xx"of the IO module 750-531
in safety related applications, the modules belonging to a safety switching device
shall be combined to form a potential group. Power to the potential group shall be
supplied via a power supply module 750-601 or 750-602 or via filter module
750-626. Either a power supply module or a separation module without power
jumper contacts (750-616) must be connected at the end of the potential group.
Pos : 82.7 /Serie 750 (WAGO-I/O-SYST EM)/Eins atz in sicherheitsg erichteten Anwendung en/Aufbau einer Potenti algruppe @ 6\mod_1259221280455_21.doc x @ 45332 @ @ 1

Figure 12: Potential Group for Safety Related Applications

Pos : 83 /D okumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Manual
Version 1.3.0
Using Interference-Free Variants of I/O Modules in Safety Related
35

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

750-531750-531/000-800

Table of Contents