Table 6 Parameter Table 140 (Additional Module Parameters) - WAGO 750 Product Manual

Table of Contents

Advertisement

750-1632/000-100
Register Name, Type
2
Parameter Table 140 (Additional Module Parameters)
Register Name, Type
0
Product manual | Version: 1.1.0
Proportional Valve Module 2-3-4
Bits, Explanation
DI2_FUNC,
0 ... 15
UINT
DI 2 function
Bits, Explanation
PWR_EN_
0 ... 15
UseStopRamp
Use of the stop ramp
UINT
with
Switch-off of the
output stage
Substitute value
strategy
Value/Range
Description
(Default)
0 (default)
Digital input
The status of DI1 is only shown in the
process image, not evaluated internally.
The value is inverted according to regis-
ter 1.
1
Limit switch, valve 2
The status of DI2 is shown in the process
image and is evaluated internally if the ac-
tuator approaches a limit switch that is con-
nected to input DI2. The status of DI 2 is in-
verted according to register 1.
When the actuator approaches the limit
switch, the current is output on valve 2 ac-
cording to the substitute value strategy (Ta-
ble 51).
2
STOP, valve 2
The current setpoint "0" is approached with
a stop ramp as long as the stop button is
held down.
Note:
The present target current is approached
with the ramp selected by RSEL as soon as
the button is released.
3
HOLD, valve 2
Hold current setpoint.
4
JOG+, valve 1
OR-operator with JOG_POS bit from
V1_CTRL
5
JOG−, valve 1
OR-operator with JOG_POS bit from
V1_CTRL
6
JOG+, valve 2
OR-operator with JOG_POS bit from
V2_CTRL
7
JOG−, valve 2
OR-operator with JOG_POS bit from
V2_CTRL
Table 6: Parameter Table 140 (Additional Module Parameters)
Value/Range
Description
(Default)
0 (default)
Output stage switches off as quickly as
possible.
1
Output stage switches off with stop ramp.
Functions
33