Using Interference-Free Variants of I/O Modules in Safety Related ApplicationsWAGO-I/O-SYSTEM 750
Pos : 80.6 /Serie 750 (WAGO-I/O-SYST EM)/Eins atz in sicherheitsg erichteten Anwendung en/Allgemeiner Aufbau ei ner Potenti algruppe - r üc kwir kungsfr eie Vari anten @ 6\mod_1258973074755_21.doc x @ 44664 @ 23 @ 1
7.2
Connecting the IO Module to Safety Switching
Devices or Safety Modules
7.2.1

General Structure

When using the interference-free variant ".../xxx-8xx"of the IO module 750-530
in safety related applications, the modules belonging to a safety switching device
shall be combined to form a potential group. Power to the potential group shall be
supplied via a power supply module 750-601 or 750-602 or via filter module
750-626. Either a power supply module or a separation module without power
jumper contacts (750-616) must be connected at the end of the potential group.
Pos : 80.7 /Serie 750 (WAGO-I/O-SYST EM)/Eins atz in sicherheitsg erichteten Anwendung en/Aufbau einer Potenti algruppe @ 6\mod_1259221280455_21.doc x @ 45332 @ @ 1

Figure 11: Potential Group for Safety Related Applications