122 Diagnostics

Table 96: LED L/A IN, L/A OUT

Table 97: LED RUN

(200 ms on / 200 ms off)
(200 ms on / 1000 ms off)

Table 98: LED ERR

(200 ms on / 200 ms off)
(200 ms on / 1000 ms off)
(200 ms on / 200 ms off /
200 ms on / 1000 ms off)
Manual
Version 1.2.1
750-354/000-001 EtherCAT® Fieldbus Coupler, ID Switch
LED Status
Meaning
Off
No connection for the respective interface
There is a connection for the respective interface.
On
No data is being exchanged via this interface.
There is a connection for the respective interface.
Flashing
Data is being exchanged via this interface.
LED Status
Meaning
Off
The fieldbus coupler is in the INIT state.
Flashing
The fieldbus coupler is in the PREOP state.
Flashing
The fieldbus coupler is in the SAFEOP state.
On
The fieldbus coupler is in the OP state.
LED Status
Meaning
Off
The fieldbus node is ready for operation.
Flashing
The EtherCAT
of the fieldbus node.
Flashing
The fieldbus coupler has changed its EtherCAT
to an execution error.
Flashing
No process data was exchanged between the EtherCAT
master and fieldbus node within the monitoring time of
100 ms.
WAGO-I/O-SYSTEM 750
master could not activate the configuration
state due