Connection Example For Digital Inputs In Rotary Table Operating Mode; Figure 33: Connection 1 X Mode Selector Switch - WAGO -I/O-SYSTEM 750 Series Manual

4fdi 24v profisafe v2 ipar safety 4-channel digital input module profisafe v2
Hide thumbs Also See for WAGO-I/O-SYSTEM 750 Series:
Table of Contents

Advertisement

68
Connect Devices
monitored for short circuits, set the Short circuit test parameter for all inputs to
"active". You must set the Valence evaluation parameter to "Antivalent". In
addition, set the Discrepancy time parameter to the discrepancy time required for
the normally open contact of the protective door switch.
You can achieve SIL3, Cat. 4/PL e with this switching.
Pos: 40.20 /Serie 750 (WAGO-I/O-SYSTEM)/Anschließen/Anschlussbeispiele/Sonderklemmen/Anschlussbeispiele 750-066x PROFIsafe/Anschlussbeispiel 750-066x/000-003 Digitale Eingänge Betriebsart Rundtisch, Überschrift 4 + Hinweis @ 7\mod_1269875881290_21.docx @ 54637 @ 3 @ 1
7.3.2
Connection Example for Digital Inputs in Rotary Table
Operating Mode
Use of the Rotary Table Operating Mode
If you have set the Operating Mode to the "Rotary Table" value, the temporal
logic evaluation of the input bits must be performed by a suitable function block
in the safe PLC. Do not use the process image of the digital inputs in the safe PLC
without the suitable function blocks.
Pos: 40.21 /Serie 750 (WAGO-I/O-SYSTEM)/Anschließen/Anschlussbeispiele/Sonderklemmen/Anschlussbeispiele 750-066x PROFIsafe/Anschlussbeispiel 750-0661/000-003 Bild 1 x Betriebsartenwahlschalter @ 7\mod_1266390769714_21.docx @ 50910 @ @ 1

Figure 33: Connection 1 x Mode Selector Switch

Pos: 40.22 /Serie 750 (WAGO-I/O-SYSTEM)/Anschließen/Anschlussbeispiele/Sonderklemmen/Anschlussbeispiele 750-066x PROFIsafe/Anschlussbeispiel 750-066x/000-003 Text Digitale Eingänge in Betriebsart Rundtisch @ 7\mod_1269943301716_21.docx @ 54714 @ @ 1
If you have set the Operating Mode parameter to "Rotary Table" using the
WAGO parameterization tool, you can connect the normally open contacts of a
mode selector switch or several rotary table sensors to the digital inputs of the
PROFIsafe I/O module.
For more information about configuring the PROFIsafe I/O module, read section
"Parameterization of the PROFIsafe I/O Module with the WAGO
Parameterization Tool".
By setting the Operating Mode parameter to Rotary table, clock output T2 is
switched off by the PROFIsafe I/O module permanently.
Set the Short circuit test parameter for all digital inputs to "active" and the Dual
channel evaluation parameter to "no".
Then connect the normally open contacts of the mode selector switch to the digital
inputs and the common clock line of the mode selector switch to clock output T1.
WAGO-I/O-SYSTEM 750
753-661/000-003 4FDI 24V PROFIsafe V2 iPar
Version 1.4.0, valid from HW/SW Version 01/02
Manual