Diagnostics

11

11.1 Diagnostics via Indicators

Supply Voltage Status
The 1L and 2L LEDs indicate the status of the supply voltages.
LED
1L
2L
System Status
The SYS LED indicates the status of the system (product).
LED
SYS
(system status)
Status of the Field-Side Functions
The FLD LED indicates the status of the field-side functions.
LED
FLD
Application Status
The APL LED indicates the status of the application.
Product manual | Version: 2.2.0
16DO FLD PN DC 24V 2.0A
Color
State
Duo LED, red/green
Green
On
Off
Off
Duo LED, red/green
Green
On
Red
On
Red
Flashing
Off
Off
Color
State
Duo LED, yellow/green
Green
On
Yellow/green
Flashing 4 Hz, alter-
nating colors
Yellow
On
Off
Off
Color
State
Duo LED, green/yellow (yellow = simultaneously red and green)
Green
On
Green
Flashing (1 Hz)
Green
Flashing (4 Hz)
Yellow
On
Off
Off
Diagnostics
Table 54: Supply Voltage Status, 1L and 2L
Description
1L supply voltage OK
No 1L supply voltage
2L supply voltage ok
2L undervoltage (voltage between 11 V and
18 V)
2L overvoltage (voltage above 30 V)
No 2L supply voltage
Table 55: System Status
Description
System status: OK Firmware is being exe-
cuted.
Firmware update active
During the firmware update, an error was
detected, e.g., a checksum error.
No power supply
Table 56: Field LED
Description
Normal operating state
Force mode is active
WAGO IO-Link Configurator is connected
to the module
Configuration error
Non-operational; no voltage