Abort Conditions — Shutdown Errors
Abort conditions are displayed on the Alarm screen and the Event History screen. The
following conditions initiate the audible and visual alarms. Since they are shut down errors,
they will cause a zone or system shut down situation based on the PCM setting.
Table 9-6
Abort Over Temp
Abort Under Temp
Circuit Overload
Configuration
Control Card Over Temperature A control card temperature has exceeded 76 °C (170 °F).
Fuse 1 Blown
Fuse 2 Blown
Earth Leakage Limit
Lost Thermocouple
Maximum Temp Limit
No Response
Over Current Limit
Receive Data Comm
104
v 1.1 — July 2015
Shutdown Errors
Shut Down Error
A zone's actual temperature has exceeded its setpoint by the
amount set for the abort limit.
A zone's actual temperature has dropped below its setpoint by
the amount set for the abort limit.
The current on this zone has risen above the maximum value
allowed.
Each zone's control parameters are compared to the values sent
and received by each zone. If the values differ, then the system
will automatically correct the problem. If the problem is not
corrected after one minute, then the configuration alarm is
triggered.
Fuse 1 on this Intelligent Control Card (ICC
and needs replacing.
Fuse 2 on this Intelligent Control Card (ICC
and needs replacing.
2
ICC
: If the calculated limit or default value is exceeded, the earth
leakage error is triggered.
3
ICC
: If the measured leakage level exceeds the Earth Leakage
Fault Limit value, the earth leakage error is triggered.
This zone has a defective or open thermocouple.
The temperature on this zone has risen above the maximum
value allowed. This usually means the switching device has failed
in the closed position and the zone ran away. The factory setting
is 95 °C (200 °F) over the normal setpoint.
Altanium has been applying 96% to 100% power to this heater
for a set amount of time, and the thermocouple connected to this
zone is not responding. The thermocouple may be pinched or
the heater power wires may be broken.
The current on this zone has risen above the maximum value
allowed.
This zone has stopped receiving data from Altanium.
Altanium Matrix2
Description
2
3
or ICC
) has blown
2
3
or ICC
) has blown
Abort Conditions — Shutdown Errors