5.4.5.2

Connecting the converter to the line supply

Spring-loaded terminals are provided with the converter to connect it to the line supply.
If you connect several converters in parallel, the optional terminals for the line cabling are
available to connect to the line supply. This significantly reduces the wiring costs.
Both connection options are shown below.
Connecting a converter with standard terminals
The terminals are spring-loaded terminals.
Figure 5-19
Permissible conductor cross-sections for single-conductor connection or for connecting flexible
cables with or without end sleeves:
● 0.75 mm
● AWG: 18 ... 10
SINAMICS S210 servo drive system
Operating Instructions, 01/2019, A5E41702836B AC
X1 - line connection 3 AC - standard
... 6 mm
2
2
5.4 Connecting the converter and the motor
Installing
165