Siemens SINAMICS S210 Operating Instructions Manual page 479

Servo drive system, converter, servomotor
Hide thumbs Also See for SINAMICS S210:
Table of Contents

Advertisement

Cause:
Synchronization of the internal clock cycle to the global control telegram has failed. The internal clock cycle exhibits an
unexpected shift.
Remedy:
Only for internal Siemens troubleshooting.
Note:
PN: PROFINET
A01980
PN: cyclic connection interrupted
Reaction:
NONE
Acknowledge:
NONE
Cause:
The cyclic connection to the PROFINET controller is interrupted.
See also: r8936 (Cyclic connection status)
Remedy:
Establish the PROFINET connection and activate the PROFINET controller in the cyclic mode.
A01981
PN: Maximum number of controllers exceeded
Reaction:
NONE
Acknowledge:
NONE
Cause:
A controller attempts to establish a connection to the drive, and as a consequence exceeds the permitted number of
PROFINET connections.
The alarm is automatically withdrawn after approx. 30 seconds.
Alarm value (r2124, interpret hexadecimal):
yyyyxxxx hex: yyyy = info. 1, xxxx = info. 2
Info 1 = 0: number of RT connections exceeded
Info 1 > 0: number of IRT connections exceeded
Info 2: permitted number of connections
Remedy:
Check the configuration of the PROFINET controllers.
A01989
PN: internal cyclic data transfer error
Reaction:
NONE
Acknowledge:
NONE
Cause:
The cyclic actual values and/or setpoints were not transferred within the specified times.
Alarm value (r2124, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
Correctly set T_io_input or T_io_output.
A02007
Function generator: Drive not SERVO / VECTOR / DC_CTRL
Reaction:
NONE
Acknowledge:
NONE
Cause:
The drive object specified for connection is not a SERVO / VECTOR or DC_CTRL.
Remedy:
Use a SERVO / VECTOR / DC_CTRL drive object with the corresponding number.
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
F03001
NVRAM checksum incorrect
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A checksum error occurred when evaluating the non-volatile data (NVRAM) on the Control Unit.
The NVRAM data affected was deleted.
Remedy:
Carry out a POWER ON (switch-off/switch-on) for all components.
SINAMICS S210 servo drive system
Operating Instructions, 01/2019, A5E41702836B AC
Faults and alarms
15.2 List of faults and alarms
477