Main Circuit Wirings; Line Supply - L1, L2, L3 - Siemens SIMOTICS S-1FL6 Operating Instructions Manual

Sinamics / simotics
Hide thumbs Also See for SIMOTICS S-1FL6:
Table of Contents

Advertisement

Connecting

4.2 Main circuit wirings

4.2
Main circuit wirings
4.2.1

Line supply - L1, L2, L3

200 V variant
Recommended minimum cable cross-section:
When used on the single phase power network:
FSB (0.1 kW to 0.2 kW): 0.33 mm
FSB (0.4 kW): 0.52 mm
FSC: 1.31 mm
When used on the three phase power network:
FSB: 0.33 mm
FSC: 0.52 mm
FSD (1 kW): 0.82 mm
FSD (1.5 kW to 2 kW): 2.08 mm
400 V variant
Recommended minimum cable cross-section:
FSAA and FSA: 1.5 mm
FSB and FSC: 2.5 mm
Note
For 200 V variant servo drive, when using the FSB and FSC on the single phase power
network, you can connect the power supply to any two connectors of L1, L2, and L3.
Assembling the line supply cable terminals
The procedure of assembling a line supply cable terminal is the same as that for a power
cable terminal on the drive side.
For more information, see Section "Assembly of cable terminals on the drive side
(Page 283)".