Faults and alarms
15.2 List of faults and alarms
Remedy:
- carry out a POWER ON (switch-off/switch-on). After switching on, the module reboots from the valid parameterization (if
available).
- restore the valid parameterization.
Examples:
a) Carry out a first commissioning, save, carry out a POWER ON (switch-off/switch-on).
b) Load another valid parameter backup (e.g. from the memory card), save, carry out a POWER ON (switch-off/switch-on).
Note:
If the fault situation is repeated, then this fault is again output after several interrupted boots.
A01019
Writing to the removable data medium unsuccessful
Reaction:
NONE
Acknowledge:
NONE
Cause:
The write access to the removable data medium was unsuccessful.
Remedy:
Remove and check the removable data medium. Then run the data backup again.
A01020
Writing to RAM disk unsuccessful
Reaction:
NONE
Acknowledge:
NONE
Cause:
A write access to the internal RAM disk was unsuccessful.
Remedy:
Adapt the file size for the system logbook to the internal RAM disk (p9930).
F01023
Software timeout (internal)
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
An internal software timeout has occurred.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade firmware to later version.
- contact Technical Support.
F01030
Sign-of-life failure for master control
Reaction:
OFF3
Acknowledge:
IMMEDIATELY
Cause:
For active PC master control, no sign-of-life was received within the monitoring time.
The master control was returned to the active BICO interconnection.
Remedy:
Set the monitoring time higher at the PC or, if required, completely disable the monitoring function.
The monitoring time is set as follows using the commissioning tool:
<Drive> -> Commissioning -> Control panel -> Button "Fetch master control" -> A window is displayed to set the monitoring
time in milliseconds.
Notice:
The monitoring time should be set as short as possible. A long monitoring time means a late response when the
communication fails!
F01031
Sign-of-life failure for OFF in REMOTE
Reaction:
OFF3
Acknowledge:
IMMEDIATELY
Cause:
With the "OFF in REMOTE" mode active, no sign-of-life was received within 3 seconds.
Remedy:
- check the data cable connection at the serial interface for the Control Unit (CU) and operator panel.
- check the data cable between the Control Unit and operator panel.
426
SINAMICS S210 servo drive system
Operating Instructions, 01/2019, A5E41702836B AC