10.1.12

Brake data

The holding brake is used to clamp the motor shaft when the motor is at a standstill. The holding
brake is not a working brake for braking the rotating motor. When the motor is at a standstill, the
holding brake is designed for at least 5 million switching cycles.
Limited EMERGENCY STOP operation is permissible. Take into account the maximum
permissible individual operating energy as well as service life, total operating energy of the
brake.
Unintentional movements through inadequate braking effect
If you use the holding brake incorrectly, e.g. as an operating brake or you ignore the
permissible operating energy of the brake, then the brake will be subject to excessive and
impermissible wear. As a consequence, there may be no brake effect. Unintentional
movements of the machine or system can result in death or serious injury.
● Observe the permissible number of operating cycles and EMERGENCY STOP properties.
● Operate the motor only in conjunction with an intact brake.
● Avoid repeated brief acceleration of the motor against a holding brake that is still closed.
The holding brakes of the 1FK2 have a torsional backlash of less than 1.5°.
The following table lists additional technical data regarding the holding brakes for operation
with a SINAMICS S210 converter from firmware version 5.2.
Motor type
Holding torque
at 120 °C
M
4
1FK2☐02
0.32
1FK2☐03
1.3
1FK2☐04
3.3
Maximum three EMERGENCY STOP operations in sequence
1)
Available soon
2)
Holding torque M
The holding torque M
operation without slip (holding function when motor is at standstill). The data applies for the
state at operating temperature (120 °C).
Dynamic braking torque M
The dynamic braking torque M
for an EMERGENCY STOP.
Opening time and closing time
The delay times that occur when switching the brake.
Maximum permissible single operating energy
SINAMICS S210 servo drive system
Operating Instructions, 01/2019, A5E41702836B AC
WARNING
Dyn. braking
torque
M
/ Nm
/ Nm
1m
0.32
1.3
3
4
is the highest permissible torque for the closed brake in steady-state
4
1m
10.1 Technical data and properties of the motor
Opening time
Closing time
t / ms
t / ms
25
8
40
10
110
15
is the smallest mean dynamic braking torque that can occur
1m
Technical specifications
Maximum per‐
Total operating
missible individ‐
energy (service
ual operating
life)
energy
1)
W / J
W
max
7.4
1.75
62
17.5
270
120
/ kJ
295