Remedy:
Check the parameter indicated in the fault value and correctly adjust it accordingly.
For fault value = 600:
Parameter p0600 must be set to the values 1, 2 or 3 in accordance with the assignment of the internal encoder evaluation
to the encoder interface.
Value 1 means: The internal encoder evaluation is assigned to the encoder interface 1 via p0187.
Value 2 means: The internal encoder evaluation is assigned to the encoder interface 2 via p0188.
Value 3 means: The internal encoder evaluation is assigned to the encoder interface 3 via p0189.
- if necessary, the internal encoder evaluation must be assigned to an encoder interface via parameters p0187, p0188 or
p0189 accordingly.
- if necessary, upgrade the firmware to a later version.
F01015
Internal software error
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
An internal software error has occurred.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade firmware to later version.
- contact Technical Support.
A01016
Firmware changed
Reaction:
NONE
Acknowledge:
NONE
Cause:
At least one firmware file in the directory was illegally changed on the non-volatile memory (memory card/device memory)
with respect to the version when shipped from the factory.
Alarm value (r2124, interpret decimal):
0: Checksum of one file is incorrect.
1: File missing.
2: File too many.
3: Incorrect firmware version.
4: Incorrect checksum of the back-up file.
Remedy:
For the non-volatile memory for the firmware (memory card/device memory), restore the delivery condition.
Note:
The file involved can be read out using parameter r9925.
The status of the firmware check is displayed using r9926.
F01018
Booting has been interrupted several times
Reaction:
NONE
Acknowledge:
POWER ON
Cause:
Module booting was interrupted several times. As a consequence, the module boots with the factory setting.
Possible reasons for booting being interrupted:
- power supply interrupted.
- CPU crashed.
- parameterization invalid.
SINAMICS S210 servo drive system
Operating Instructions, 01/2019, A5E41702836B AC
Faults and alarms
15.2 List of faults and alarms