Preparations
1. Install the motor and converter according to the specifications in the following section:
2. Mount the motor on the mechanical system. Connect the motor to the converter.
3. Connect the converter to your commissioning device via the service interface (X127).
4. Switch the converter on.
The converter powers up and reads the motor data.
5. Start the browser for commissioning.
6. Enter the IP address of the converter in the input line of your browser.
Default IP address: 169.254.11.22
Interfaces and connection type
Using the default configuration of the web server, you can access the SINAMICS frequency
converter using the service interface (X127) - both via an HTTP connection as well as via an
encrypted HTTPS connection.
In the standard configuration, interface X150 is deactivated for web server access operations.
If the X150 interface is activated to access the web server, then access can only take place via
a secure HTTPS connection.
For details on this, see:
NOTICE
Software manipulation when using non-encrypted connections (HTTP)
The HTTP protocol transfers data without encryption. This facilitates password theft, for
example, and can lead to data manipulation by unauthorized parties and thus ultimately to
damage.
● Limit access to HTTPS connections so that all data is transferred encrypted.
6.1.2
Users and access rights
There are 2 pre-defined users for access to the converter via the Web server:
● Administrator
The user "Administrator" has full access to the converter data displayed in the web server.
A password is always required for access as administrator.
● SINAMICS
The "SINAMICS" user has restricted access rights, see the following table. Per default, a
password is not assigned for the SINAMICS user.
SINAMICS S210 servo drive system
Operating Instructions, 01/2019, A5E41702836B AC
Installing (Page 139)
"Configuring the IP connection (Page 243)"
Commissioning and diagnostics using the web server
6.1 Fundamentals