r5293
FFT tuning speed controller P gain identified
Data type: FloatingPoint32
Description:
Displays the determined proportional gain Kp of the speed controller before FFT tuning.
This function is used for One Button Tuning (p5300 = 1).
Dependency:
See also: p5291
p5296[0...2]
Controller optimization noise amplitude
Can be changed: T, U
Min: 1.0 [%]
Description:
The drive determines the noise amplitude for One Button Tuning and writes the value to p5296.
Dependency:
See also: p5291
p5300[0]
One Button Tuning selection
Can be changed: T
Min: -1
Description:
Setting to activate/deactivate the One Button Tuning function.
If p5300 = 1:
The One Button Tuning function is configured using p5271 and p5301.
Value:
-1:
0:
1:
Dependency:
The motor must have already been commissioned so that One Button Tuning functions perfectly.
The One Button Tuning function is configured using p5271 and p5301.
The required dynamic performance of the control loop is set in p5292.
The traversing path for the test signal is parameterized in p5308.
Additional relevant parameters
p5309, p5296, p5297, r5274
See also: p5271, r5274, p5292, r5293, p5296, p5301, p5308, p5309
Note
If p5300 = -1:
One Button Tuning is deactivated and p5300 is automatically set = 0. Further, the presetting values for the speed
controller are restored.
If p5300 = 0:
To permanently save the values for the speed controller that have been determined, the parameters must be saved in
a non-volatile memory.
If p5300 = 1:
One Button Tuning is active.
The moment of inertia is determined once using a test signal. The controller parameters and current setpoint filters are
additionally determined once using a noise signal as excitation source. The steps to be executed can be configured
using p5301.
p5301[0]
One Button Tuning configuration 2
Can be changed: T, U
Min: -
Description:
Setting the functions for One Button Tuning (p5300 = 1).
A test signal is required for some functions. Here, parameters p5307 to p5309 must be a taken into consideration.
Bit field:
Bit
00
01
02
SINAMICS S210 servo drive system
Operating Instructions, 01/2019, A5E41702836B AC
Reset controller parameters
Inactive
One Button Tuning
Signal name
Setting the proportional gain Kp
Setting current setpoint filter
Estimate moment of inertia
Unit: [Nms/rad]
Data type: FloatingPoint32
Max: 300.0 [%]
Data type: Integer16
Max: 1
Data type: Unsigned32
Max: -
Parameters
14.2 List of parameters
Def: [0] 10.0 [%] , [1] 30.0 [%] , [2] 5.0
[%]
Def: 0
Def: 0000 0000 0000 0111 bin
1 signal
0 signal
Yes
No
Yes
No
Yes
No
385