Faults and alarms
15.2 List of faults and alarms
Remedy:
Not necessary.
The message is automatically withdrawn when the test stop has been completed.
Note:
SI: Safety Integrated
A30799
SI Motion P2: Acceptance test mode active
Reaction:
NONE
Acknowledge:
NONE
Cause:
The acceptance test mode is active.
This means that the setpoint speed limiting is deactivated (r9733).
Remedy:
Not necessary.
The message is automatically withdrawn when exiting the acceptance test mode.
Note:
SI: Safety Integrated
N30800
Power unit: Group signal
Reaction:
OFF2
Acknowledge:
NONE
Cause:
The power unit has detected at least one fault.
Remedy:
Evaluate the other messages that are presently available.
F30805
Power unit: EEPROM checksum error
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
Internal parameter data is corrupted.
Fault value (r0949, interpret hexadecimal):
01: EEPROM access error.
02: Too many blocks in the EEPROM.
Remedy:
Replace the module.
F30895
power module DRIVE-CLiQ: Alternating cyclic data transfer error
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communication error has occurred from the power unit to the Control Unit involved.
Fault cause:
11 (= 0B hex):
Synchronization error during alternating cyclic data transfer.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
Carry out a POWER ON (switch-off/switch-on).
F30899
Power unit: Unknown fault
Reaction:
NONE
Acknowledge:
IMMEDIATELY