Siemens SINAMICS S210 Operating Instructions Manual page 277

Servo drive system, converter, servomotor
Hide thumbs Also See for SINAMICS S210:
Table of Contents

Advertisement

Operation with SD card without firmware
Procedure
1. You replace the converter as described above in steps 1. ... 5.
2. Case 1, the new converter has the same or a higher firmware version:
– When it runs up, the converter takes the settings from the card, and after it has run up
– Switch the converter off and on again.
Case 2, the new converter has an older firmware version:
– The converter is reset to the factory settings once it has run up. You can recognize this
You have now replaced the converter.
SINAMICS S210 servo drive system
Operating Instructions, 01/2019, A5E41702836B AC
commissioning has been completed. For a higher firmware version, then the DQ
components are updated (encoder).
as the dialog screen form is displayed in the web server for the first login.
In this case, switch off the converter without saving – and withdraw the SD card from the
converter.
Restore the firmware to the version that was on the replaced converter.
Note
Review the machine documentation, or check which version is installed on the other
S210 converters in the machine.
Converter firmware update (Page 268)
Switch off the converter, insert the SD card with converter settings into the converter and
switch the converter on again.
When it runs up, the converter takes the settings from the card, and after it has run up
commissioning has been completed.
Save the settings in the web server in a non-volatile fashion using
Service and maintenance